RE-2Y(St)H & RE-2X(St)H-MP
HALOGEN-FREE INSTRUMENTATION CABLES, EN 50288-7RE-2Y(St)H,SINGLE & MULTI-PAIR, PE INSULATED, COLLECTIVE SCREENED, HFFR SHEATHEDRE-2X(St)H,SINGLE & MULTI-PAIR, XLPE INSULATED, COLLECTIVE SCREENED, HFFR SHEATHED
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... These cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
Sheath colour: RAL 9005, Black or RAL 5015, Blue
Conductor: Plain copper wire, stranded, IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
Insulation (2Y): PE compound, EN 50290-2-23; (RE-2Y….)
Insulation (2X): XLPE compound, EN 50290-2-29; (RE-2X….)
Core identification: Black / White cores numbered 1-1, 2-2,…, Upon request ; Colour coded according to IEC 60189-2, Other core configurations manufactured upon request.
Pair: Two conductors twisted to a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Screen: AL-PES tape over stranded tinned copper drain, wire 0,50 mm2
Outer sheath: HFFR compound, EN 50290-2-27
Capacitance unbalance: (1 kHz) : max. 500 pF/500 m
Standard: TS/DIN EN 50288-7
Insulation thickness: 0,50mm2 : 0,40 mm, 0,75mm2 : 0,40 mm, 1,0mm2 : 0,40 mm, 1,3mm2 : 0,45 mm, 1,5mm2 : 0,45 mm
Conductor resistance: 0,50mm2 : 36,7 Ω/km, 0,75mm2 : 25,0 Ω/km, 1,0mm2 : 18,5 Ω/km, 1,3mm2 : 14,2 Ω/km, 1,5mm2 : 12,3 Ω/km
Insulation resistance: Min. 5000 MΩ.km
L / R (ratio) (max.): 0,50mm2 : 25 µH/Ω, 0,75mm2 : 25 µH/Ω, 1,0mm2 : 25 µH/Ω1,30mm2 : 40 µH/Ω, 1,5mm2 : 40 µH/Ω
Rated voltage: 300V
Test voltage: Urms core-core : 1500 V, Urms core-screen : 1500 V
Temperature range (2Y): operation : - 30 oC ~ + 70 oC, ınstallation : - 5 oC ~ + 50 oC
Temperature range (2X): operation : - 30 oC ~ + 90 oC, ınstallation : - 5 oC ~ + 50 oC
Smoke density test: IEC 61034-2 & TS/DIN EN 61034-2
Min. bending radius: 7,5 x D
Halogen-free properties test: IEC60754-1/2 & TS/DIN EN 50267-2
Flame test: IEC 60332-1 & TS/DIN EN 60332-1, IEC 60332-3 & TS/DIN EN 50266-2-4